Iris dampers are used for air flow rate adjustment and measurement in round air ducts. A uniform air flow rate occurs in the duct cross section due to its decreasing orifice structure. Closure of the iris damper creates a uniform air flow rate adjustment with a homogenous air flow. There are manometer connections in order to measure the differential pressure in dampers. The measurement accurancy of the damper is ±%5 and the operating temperature is between -10°C and +80°C. Also, the connections should be sealed to prevent air leakage.
ØD(mm): Iris damper flange diameter |
Ød(mm): Iris damper nominal diameter |
L (mm): Iris damper length |